Thermometrics RTD-70 through RTD-90 series are complete industrial Pt100 assemblies with a metal-sheathed probe, process connection, and weatherproof or explosion-proof connection head. The parallel of the TC-70 through TC-90 series for high-accuracy applications requiring RTD performance.
| Model | Name | Fitting | Extension | Head | Best For |
|---|---|---|---|---|---|
| RTD-70 | Pt100 Industrial RTD — Fixed Head | Fixed ½" NPT | None | Aluminum Form B, NEMA 4X | General process; plant DCS; fixed installation |
| RTD-71 | Pt100 Industrial RTD — Adjustable Fitting | Adjustable compression fitting | None | Aluminum Form B, NEMA 4X | Retrofit; variable insertion depth applications |
| RTD-80 | Pt100 Industrial RTD — Nipple-Union Extension | Fixed NPT + nipple/union | 2" to 12" nipple | Aluminum or cast iron | Insulated piping; head clearance over insulation |
| RTD-90 | Pt100 Remote Mount RTD Assembly | Fixed NPT | Flexible conduit or armored cable | Remote-mount head | High-vibration areas; high ambient temperature |
| Parameter | Specification |
|---|---|
| Sensing Element | Pt100 wire-wound or thin-film, IEC 60751 |
| Accuracy Class | Class A standard (±0.15°C @ 0°C); Class AA or B available |
| Wire Config | 3-wire standard; 4-wire available |
| Sheath OD | 1/4" (6.4mm) standard; 3/16" and 3/8" available |
| Sheath Material | 316SS standard; Inconel 600 for high-temp service |
| Process Connection | 1/2" NPT standard; 3/4" NPT, BSP, flanged available |
| Insertion Length | 2" to 24" standard; custom to 60" |
| Temperature Range | −200°C to 600°C (standard sheath); to 850°C on request |
| Connection Head | Aluminum Form B (NEMA 4X std); cast iron; SS; NEMA 7/9 XP |
| Transmitter Insert | DIN head-mount 4–20mA HART transmitter available |
Head-mount 4–20mA HART transmitters insert directly into the Form B connection head on RTD-70 and RTD-80 assemblies. The transmitter converts the Pt100 signal to a two-wire 4–20mA current loop, eliminating the need for a separate transmitter housing, conduit run, and power supply. Configured for sensor type, range, and fail-safe direction before shipment.
Talk directly to the engineering team that builds your assemblies. No bots, no call centers.